What are regulations on surfaces and spaces of fire access and parking lots for fire engines in Vietnam?

What are regulations on surfaces and spaces of fire access and parking lots for fire engines in Vietnam? Thank you!

Pursuant to Section 6.2.3 to Section 6.2.9 of the national technical regulations on fire safety for buldings and constructions issued together with the Circular 02/2021/TT-BXD stipulating surfaces and spaces of fire access and parking lots for fire engines in Vietnam as follows:

6.2.3. Parking lots for fire engines must guarantee that the horizontal distance from edges of the parking lots that are nearest to the buildings to the middle point of elevated entrances is no closer than 2 m and no further than 10 m.

6.2.4 Surfaces of parking lots for firefighting must be even. If situated on a tilted surface, slope must not exceed 1:15. Slope of driveways for fire engines must not exceed 1:8.3.

6.2.5. If length of dead end fire access or parking lots for fire engines is larger than 46 m, situate U-turn lots designed according to 6.4 at the end of the dead end sections.

6.2.6. Public roads can be used as parking lots for fire engines, if positioning of said roads conforming to regulations on distances to elevated entrances under 6.2.3.

6.2.7. Fire access and parking lots for fire engines must be clear at all time. Spaces between parking lots for fire engines and elevated entrances must not be obstructed by trees or other immovable objects.

6.2.8. Mark all corners of fire access and parking lots for fire engines other than public roads utilized as fire access or parking lots for fire engines. Marking must be implemented by reflective paints to ensure visibility at night and positioned at both sides of fire access or parking lots for fire engines no further than 5 m.

At the beginning and end sections of fire access or parking lots for fire engines, install warning signs with white background, red letters and height of each letter not less than 50 mm. Height from ground level to the lowest points of the signs must range from 1.0 m to 1.5 m. Signs must be visible at night and must not be more than 3 m away from fire access or parking lots for fire engines. All parts of fire access or parking lots for fire engines must not be more than 15 m away from the nearest signs.

6.2.9. Surfaces of fire access and parking lots for fire engines must be able to withstand vehicular weight of the fire engines according to design requirements and satisfactory to vehicle types of Police Departments of Fire Prevention and Fighting and Rescue where the constructions are built.

Best regards!

Related Posts
LawNet
What are support levels for damage from natural disasters, plant pests in Vietnam from February 25, 2025?
LawNet
Decree 18/2025/ND-CP providing guidance on the Law on Electricity related to electricity trading activities and ensuring power supply situations in Vietnam
LawNet
What is the significance of January 8? Which areas are prohibited from mineral activities in Vietnam?
LawNet
What are environmental protection tax rates for gasoline, oil, and lubricants in Vietnam January 1, 2025?
LawNet
What is the electricity transmission price until December 31, 2024 in Vietnam?
LawNet
Circular 35/2024/TT-BTNMT on technical procedures for the collection, transportation, and treatment of domestic solid waste in Vietnam
LawNet
Promulgation of the Law on Electricity 2024 in Vietnam from February 1, 2025
LawNet
Promulgation of the Law on Geology and Minerals 2024 in Vietnam
LawNet
Promulgation of the Law on Fire Prevention and Fighting and Rescue in 2024 in Vietnam
LawNet
Three cases of suspension due to failure to ensure fire prevention and fighting in Vietnam
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;