Circular 11/2018/TT-BXD has been signed and promulgated by the Ministry of Construction (Hanoi, Vietnam), issuing the National Technical Regulation on underground railway structures - QCVN 08:2018/BXD. This document amends and supplements Circular 28/2009/TT-BXD.
According to the new regulations in Vietnam, the following houses and underground railway structures must be equipped with fire alarm and extinguishing device:
House, construction, equipment | Automatic fire extinguishing device | Automatic fire alarm equipment |
Cable trench, station longitudinal pit, cable storage floor with a nominal fire load | Greater than 180 MJ/m^2^ | 180 MJ/m^2^ and less |
Ventilation cable trench | - | Regardless of area |
Electric distribution room | - | Regardless of area |
Electrical panel | - | - |
Storage warehouse for flammable oil, paint materials | Regardless of area | - |
Houses with fire hazard classification A | Regardless of area | - |
Houses with fire hazard classifications B, C | 300 m^2^ and larger | Less than 300 m^2^ |
Power and control cabinets for elevators in the machine room | - | - |
Repair and rest areas within the station stop house fire compartment | 4500 m^2^ and larger | Less than 4500 m^2^ |
More details can be found in Circular 11/2018/TT-BXD which takes effect in Vietnam from March 15, 2019.