What is a fire compartment? What is the definition of a fire compartment in Vietnam? What are the requirements for a fire compartment in Vietnam?

What is a fire compartment? What is the definition of a fire compartment in Vietnam? What are the requirements for a fire compartment in Vietnam?

What is a fire compartment?

Pursuant to National Technical Regulation QCVN 06:2021/BXD on Fire Safety for Houses and Buildings stipulating as follows:

Fire Compartment:

The transitional space between two doors used to protect against the intrusion of smoke and other gases when entering a house, staircase, or other rooms within the building.

What is a fire compartment? What is the definition of a fire compartment in Vietnam? What are the requirements for a fire compartment in Vietnam? - image from internet

What is the definition of a fire compartment in Vietnam? What are the requirements for a fire compartment in Vietnam?

Fire Compartment:

The fire compartment consists of constituent parts with specified fire resistance limits as required by the regulations (see 2.4.3).

Requirements for fire compartment:

The fire-resistant parts are classified according to the fire resistance limits of their separating elements as shown in Table 1. When the fire compartment includes doors, gates, hatches, air valves, windows, screens (referred to collectively as fire doors and valves), or when these doors are located in the fire compartment (referred to as fire compartment doors), the fire doors, valves, and fire compartment must be selected to have appropriate fire resistance capabilities corresponding to the type of fire compartment as specified in Table 1.

The fire resistance limits of different types of fire doors and valves in the fire compartment are specified in Table 2.

The fire resistance limits of the components of the fire compartment (walls, floors, fire doors, and valves) at the fire doors and valves in the fire compartment must comply with the regulations specified in Table 3.

Type 1 fire compartment components must belong to fire hazard level K0. In specific cases, the use of fire hazard level K1 is permitted for type 2 to type 4 fire compartment components.

Table 1 - Classification of fire compartment components

Fire compartment components

Types of fire compartment component

The fire resistance limit of the fire compartment components shall not be less than

The type of fire doors and valves in the fire compartment shall not be less than

The type of fire compartment shall not be less than

1. Fire wall.

1

REI 150

1

1

2

REI 45

2

2

2. Fire partition.

1

EI 45

2

1

2

EI 15

3

2

3. Fire floor.

1

REI 150

1

1

2

REI 60

2

1

3

REI 45

2

1

4

REI 15

3

2

 

Table 2 - The fire resistance limit of fire doors and valves in the fire compartment.

Fire doors and valves in the fire compartment

Types of fire door and valve in the fire compartment

The fire resistance limit shall not be less than

1. Doors, gates, hatches, valves 1)

1

EI 60

2

EI 30 2)

3

EI 15

2. Windows

1

E 60

2

E 30

3

E 15

3. Screens

1

EI 60

1) The fire resistance limit of fire valves is allowed to be determined based only on integrity (E) if these valves are installed within channels, shafts, and conduits that ensure the required fire resistance capability, both for integrity (E) and insulation (I).

2) The fire resistance limit of elevator shaft doors is allowed to be at least E 30.

Table 3 - Fire resistance limits of fire compartment components for doors and fire doors in the fire compartment.

Types of fire compartment component

Fire resistance limits of fire compartment components shall not me less than

Fire partitions of the fire compartment components

Fire floor of the fire compartment components

Doors and valves of the fire compartment components

1

EI 45

REI 45

EI 30

2

EI 15

REI 15

EI 15

Best regards!

Related Posts
LawNet
Guidelines on criteria for identifying temporary and dilapidated houses in Vietnam in 2025
LawNet
What is the template of Application for a construction permit for detached house in Vietnam in 2025?
LawNet
What is the template of the Application for reissue of construction permit for detached house in 2025 in Vietnam?
LawNet
What is the template of the Report for appraising the feasibility study for construction investment in accordance with Decree 175 in Vietnam?
LawNet
Promulgation of Circular 11/2024/TT-BXD on codes, title standards; standards and conditions for promotion consideration of public employees in the Construction sector in Vietnam
LawNet
Will the Urban and Rural Planning Law 2024 in Vietnam be effective from July 1, 2025?
LawNet
From January 1, 2025, will the district-level town Phong Dien beestablished under Hue city?
LawNet
From January 1, 2025, is it correct that Hue will become a central-affiliated city of Vietnam?
LawNet
Where is Ly Son Island? What are detailed regulations on striving for Ly Son island district to become a center by 2030?
LawNet
Promulgation of Circular 94/2024/TT-BQP providing detailed provisions on certain articles of the Law on Housing in the People's Army of Vietnam
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;