Pursuant to Section 6.2.1 of the national technical regulations on fire safety for buldings and constructions issued together with the Circular 02/2021/TT-BXD stipulating general requirements of fire access and parking lots for fire engines in Vietnam as follows: 

- Clearance width of fire access for fire engines must not be less than 3.5 m.

- Clearance width of parking lots for fire engines must ensure accessibility for deployment of fire-fighting facilities satisfactory to fire service height and fire hazard of buildings mentioned in Schedule 14.

Schedule 14 - Regulations on dimensions of parking lots for firefighting

Fire hazard levels by functions/Dimension criteria of parking lots

Dimensions of parking lots for fire enginesm, based on height of buildings, m

 

≤ 15

> 15 and ≤ 281)

> 28

1. F1.3 buildings

 

 

 

a) Width of parking lots for fire engines

Not required

≥ 6

≥ 6

b) Length of parking lots for fire engines

Not required

≥ 15

≥ 15

2. Other building levels

 

 

 

a) Width of parking lots for fire engines

Not required

≥ 6

≥ 6

b) Length of parking lots for fire engines

Consult Schedule 15 and Schedule 16

1) Parking lots for fire engines are not required for buildings with no more than 50 people on each storey, according to Schedule G.9 (Annex G), and distance from fire access for fire engines to the hydrant boosters no more than 18 m.

- Only allow obstacles to be placed on fire access and parking lots for fire engines if all following requirements are satisfied:

+ Clearance height to enable fire-fighting facilities to travel through must not be lower than 4.5 m;

+ Dimensions of overhead obstacles (measured along length of fire access and parking lots for fire engines) must not exceed 10 m; and

+ In case of 2 or more overhead obstacles stretching across fire access or parking lots for fire engines, clearance space between the obstacles must not be lower than 20 m; and

+ Length of ends of fire access or parking lots for fire engines unobstructed by overhead obstacles must not be lower than 20 m; and

+ Length of parking lots for fire engines must not take into account sections with overhead obstacles.

- Along outer walls of buildings, install entrances to the buildings via the outer walls from elevated positions (elevated entrances) satisfactory to 6.3 to deploy firefighting and rescue activity.

Best regards!

Related Posts
LawNet
Guidelines on criteria for identifying temporary and dilapidated houses in Vietnam in 2025
LawNet
What is the template of Application for a construction permit for detached house in Vietnam in 2025?
LawNet
What is the template of the Application for reissue of construction permit for detached house in 2025 in Vietnam?
LawNet
What is the template of the Report for appraising the feasibility study for construction investment in accordance with Decree 175 in Vietnam?
LawNet
Promulgation of Circular 11/2024/TT-BXD on codes, title standards; standards and conditions for promotion consideration of public employees in the Construction sector in Vietnam
LawNet
Will the Urban and Rural Planning Law 2024 in Vietnam be effective from July 1, 2025?
LawNet
From January 1, 2025, will the district-level town Phong Dien beestablished under Hue city?
LawNet
From January 1, 2025, is it correct that Hue will become a central-affiliated city of Vietnam?
LawNet
Where is Ly Son Island? What are detailed regulations on striving for Ly Son island district to become a center by 2030?
LawNet
Promulgation of Circular 94/2024/TT-BQP providing detailed provisions on certain articles of the Law on Housing in the People's Army of Vietnam
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;