Nominal fire resistance limit of external wall structures in fire safety in Vietnam

What are regulations on nominal fire resistance limit of external wall structures in fire safety in Vietnam?

Based on Table F.3, Section F.1, Appendix F of the National Technical Regulation on Fire Safety for Buildings and Constructions issued together with Circular 02/2021/TT-BXD, the regulation on the nominal fire resistance limit of external wall structures is as follows:

Table F.3 - External Walls (non-load-bearing)

Structure and Materials Fire Resistance Limit
(1) (2)
1. Walls with a steel skeleton frame, the outer layer made of non-combustible material sheets, and the inner layer is:  
a) 12.5 mm thick cement sand or gypsum plaster on steel lath EI 240
b) Two 9.5 mm thick panels EI 30
c) 9.5 mm thick panel with 12.5 mm thick gypsum plaster EI 30
d) 12.5 mm thick panel with 5 mm thick gypsum plaster EI 30
e) 50 mm thick rice husk board EI 30
f) 50 mm thick rice husk board with 5 mm thick gypsum plaster EI 120
2. Walls with a wooden skeleton frame, the outer layer is 10 mm thick cement sand or cement-lime ^1)^ and the inner layer is:  
a) 16 mm thick gypsum plaster on steel lath EI 60

Table F.3 (conclusion)

(1) (2)
b) 9.5 mm thick panel with 12.5 mm thick gypsum plaster EI 60
c) 12.5 mm thick panel with 5 mm thick gypsum plaster EI 60
d) 50 mm thick rice husk board EI 60
e) Autoclaved aerated concrete block with a thickness of: EI 180
50 mm  
62 mm EI 240
75 mm EI 240
100 mm EI 240
3. Walls with a wooden skeleton frame, the outer layer is 100 mm thick brick or blocks made from fired clay, concrete, the inner layer with 16 mm thick gypsum plaster on steel lath EI 240
4. Walls with a wooden skeleton frame, the outer layer is edge-overlapping panels or 9.5 mm thick plywood ^1^^)^ and the inner layer is:  
a) 16 mm thick gypsum plaster on steel lath EI 30
b) 9.5 mm thick panel with 12.5 mm thick gypsum plaster EI 30
c) 12.5 mm thick panel with 5 mm thick gypsum plaster EI 30
d) 50 mm thick rice husk board EI 30
e) Autoclaved aerated concrete block with a thickness of:  
50 mm EI 180
62 mm EI 240
75 mm EI 240
100 mm EI 240
^1)^ The presence of membranes that can form combustible vapors within the thickness of these structures should not contribute to their fire resistance.
NOTE: Principles for determining the fire resistance limits of structural elements see 2.3.2.

Sincerely!

Related Posts
LawNet
Guidelines on criteria for identifying temporary and dilapidated houses in Vietnam in 2025
LawNet
What is the template of Application for a construction permit for detached house in Vietnam in 2025?
LawNet
What is the template of the Application for reissue of construction permit for detached house in 2025 in Vietnam?
LawNet
What is the template of the Report for appraising the feasibility study for construction investment in accordance with Decree 175 in Vietnam?
LawNet
Promulgation of Circular 11/2024/TT-BXD on codes, title standards; standards and conditions for promotion consideration of public employees in the Construction sector in Vietnam
LawNet
Will the Urban and Rural Planning Law 2024 in Vietnam be effective from July 1, 2025?
LawNet
From January 1, 2025, will the district-level town Phong Dien beestablished under Hue city?
LawNet
From January 1, 2025, is it correct that Hue will become a central-affiliated city of Vietnam?
LawNet
Where is Ly Son Island? What are detailed regulations on striving for Ly Son island district to become a center by 2030?
LawNet
Promulgation of Circular 94/2024/TT-BQP providing detailed provisions on certain articles of the Law on Housing in the People's Army of Vietnam
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;