Nominal fire resistance limit of external wall structures in fire safety in Vietnam
Based on Table F.3, Section F.1, Appendix F of the National Technical Regulation on Fire Safety for Buildings and Constructions issued together with Circular 02/2021/TT-BXD, the regulation on the nominal fire resistance limit of external wall structures is as follows:
Table F.3 - External Walls (non-load-bearing)
Structure and Materials | Fire Resistance Limit |
(1) | (2) |
1. Walls with a steel skeleton frame, the outer layer made of non-combustible material sheets, and the inner layer is: | |
a) 12.5 mm thick cement sand or gypsum plaster on steel lath | EI 240 |
b) Two 9.5 mm thick panels | EI 30 |
c) 9.5 mm thick panel with 12.5 mm thick gypsum plaster | EI 30 |
d) 12.5 mm thick panel with 5 mm thick gypsum plaster | EI 30 |
e) 50 mm thick rice husk board | EI 30 |
f) 50 mm thick rice husk board with 5 mm thick gypsum plaster | EI 120 |
2. Walls with a wooden skeleton frame, the outer layer is 10 mm thick cement sand or cement-lime ^1)^ and the inner layer is: | |
a) 16 mm thick gypsum plaster on steel lath | EI 60 |
Table F.3 (conclusion)
(1) | (2) |
b) 9.5 mm thick panel with 12.5 mm thick gypsum plaster | EI 60 |
c) 12.5 mm thick panel with 5 mm thick gypsum plaster | EI 60 |
d) 50 mm thick rice husk board | EI 60 |
e) Autoclaved aerated concrete block with a thickness of: | EI 180 |
50 mm | |
62 mm | EI 240 |
75 mm | EI 240 |
100 mm | EI 240 |
3. Walls with a wooden skeleton frame, the outer layer is 100 mm thick brick or blocks made from fired clay, concrete, the inner layer with 16 mm thick gypsum plaster on steel lath | EI 240 |
4. Walls with a wooden skeleton frame, the outer layer is edge-overlapping panels or 9.5 mm thick plywood ^1^^)^ and the inner layer is: | |
a) 16 mm thick gypsum plaster on steel lath | EI 30 |
b) 9.5 mm thick panel with 12.5 mm thick gypsum plaster | EI 30 |
c) 12.5 mm thick panel with 5 mm thick gypsum plaster | EI 30 |
d) 50 mm thick rice husk board | EI 30 |
e) Autoclaved aerated concrete block with a thickness of: | |
50 mm | EI 180 |
62 mm | EI 240 |
75 mm | EI 240 |
100 mm | EI 240 |
^1)^ The presence of membranes that can form combustible vapors within the thickness of these structures should not contribute to their fire resistance. | |
NOTE: Principles for determining the fire resistance limits of structural elements see 2.3.2. |
Sincerely!
What is construction permit according to the law in Vietnam? What documents are required for Application for a construction permit for detached houses in Vietnam?
Is a permit required for relocating a construction project in Vietnam? What documents are included in the Application for a construction relocation permit in Vietnam?
What day is November 8? What are contents of Management Regulations according to urban planning project, urban design in Vietnam?
Which Construction Price Indices are Determined by Project, Type of Project?
Legal Basis for National Land Use Planning and Planning under the Latest Regulations
Period of Land Use Planning and Plan According to the Latest Regulations
What is a Rural Market?
What is a Temporary Market?
What is a Public Market?
What is a General Market?