How many times a year is the apartment building fire alarm system inspected?

According to the law, how many times is the automatic fire alarm system of an apartment building inspected per year? Looking forward to your prompt response.

In Section 6 of the Vietnam Standards TCVN 3890:2009, regulations regarding the inspection and maintenance of automatic fire alarm systems are stipulated as follows:

- The automatic fire alarm system, after installation, must undergo a full operational test. The automatic fire alarm system is only permitted to be put into operation when the test results show that the system fully meets the design requirements and related standards.

- The automatic fire alarm system, after being put into operation, must be inspected at least twice a year. During the inspection, all functions of the system and the operational capability of all system devices must be tested.

- The periodic maintenance of the automatic fire alarm system is carried out depending on the environmental conditions of the installation location and according to the manufacturer’s regulations, but at least once every two years, a full maintenance of the system must be organized. The maintenance must include a comprehensive inspection of the operation of all devices in the system.

=> Thus, according to the above regulations, the automatic fire alarm system of the apartment building must be inspected at least twice a year.

Sincerely.

Related Posts
LawNet
Management of construction project surveys in the Ministry of National Defense of Vietnam
LawNet
What are the regulations on management of construction surveys within the Ministry of National Defense of Vietnam?
LawNet
Requirements for fire safety distances for residential buildings, public works, and auxiliary facilities of industrial establishments in Vietnam
LawNet
Requirements for fire safety distances for buildings and industrial works in Vietnam
LawNet
What is the highest permissible floor for arranging lecture halls, conference rooms in public buildings in Vietnam?
LawNet
Nominal fire resistance limit of external wall structures in fire safety in Vietnam
LawNet
Nominal fire resistance limit of reinforced concrete beams in Vietnam
LawNet
Nominal fire resistance limit of pre-stressed reinforced concrete beams in Vietnam
LawNet
Nominal fire resistance limits of reinforced concrete columns in fire safety in Vietnam
LawNet
Nominal fire resistance limits of aluminum structures in fire safety in Vietnam
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;