Airflow and Smoke Exhaust Duct Design in Smoke Protection for Buildings and Structures

How are the airflow and smoke vent pipe design regulated in smoke protection for buildings and structures? I need to learn about these issues. Please provide guidance.

Flow and Design of Smoke Extraction Ducts in Smoke Protection for Buildings and Structures are regulated from Section D.4 to Section D.8 Appendix D of the National Technical Regulation on Fire Safety for Buildings and Structures issued together with Circular 02/2021/TT-BXD as follows:

D.4 **** Smoke extraction flow must be calculated under the following circumstances:

a) From the corridors mentioned in paragraphs a), b), c), and d) of D.2 - for each segment length not exceeding 60 m.

b) From the rooms mentioned in e), f), g), and h) of D.2 - for each smoke zone with an area not exceeding 3,000 m².

NOTE: The calculation of smoke extraction flow must comply with current standards, considering factors such as fire load, temperature, combustion products generated, external air parameters, geometric characteristics, and location of openings.

D.5 **** The design of the smoke extraction system for protecting corridors must be separate from the smoke extraction system for protecting rooms.

D.6 **** Smoke collection inlets of smoke extraction shafts for corridors must be placed below the ceiling of the corridors and not lower than the lintel (the upper edge of the doorway of the escape route). It is permissible to place smoke collection inlets on branches leading into the smoke extraction shaft. Each corridor segment requiring a smoke collection inlet must not exceed 30 m.

D.7 **** When extracting smoke directly from rooms with an area greater than 3,000 m², the area must be divided into smoke zones not exceeding 3,000 m² each, accounting for the possibility of a fire in one of these zones. Each smoke collection inlet should serve an area not exceeding 1,000 m².

D.8 **** Direct smoke extraction for single-story building rooms must include natural smoke extraction through ducts with valves, hatches, or non-sealed light wells.

From areas near windows, with a width of up to 15 m, smoke escape is allowed through small window openings (louvers) with the bottom edge of the openings at a height of no less than 2.2 m from the ground floor.

In multi-story buildings, there must be a mechanical forced smoke extraction system.

Best regards!

Related Posts
LawNet
Guidelines on criteria for identifying temporary and dilapidated houses in Vietnam in 2025
LawNet
What is the template of Application for a construction permit for detached house in Vietnam in 2025?
LawNet
What is the template of the Application for reissue of construction permit for detached house in 2025 in Vietnam?
LawNet
What is the template of the Report for appraising the feasibility study for construction investment in accordance with Decree 175 in Vietnam?
LawNet
Promulgation of Circular 11/2024/TT-BXD on codes, title standards; standards and conditions for promotion consideration of public employees in the Construction sector in Vietnam
LawNet
Will the Urban and Rural Planning Law 2024 in Vietnam be effective from July 1, 2025?
LawNet
From January 1, 2025, will the district-level town Phong Dien beestablished under Hue city?
LawNet
From January 1, 2025, is it correct that Hue will become a central-affiliated city of Vietnam?
LawNet
Where is Ly Son Island? What are detailed regulations on striving for Ly Son island district to become a center by 2030?
LawNet
Promulgation of Circular 94/2024/TT-BQP providing detailed provisions on certain articles of the Law on Housing in the People's Army of Vietnam
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;