Vietnam: Safety distance for petroleum projects according to Decree 25/2019/ND-CP

This is the notable content prescribed in Decree 25/2019/ND-CP of Vietnam's Government amending and supplementing Decree 13/2011/ND-CP on the safety of onshore petroleum works.

Specifically, the safe distance from liquefied petroleum gas storage tanks stored under pressure to the protected objects and the distance between the storage tanks is stipulated in Decree 25/2019/ND-CP of Vietnam's Government as follows:

Tank capacity, V (m3)

Safety distance (m)

Distance between tanks (m)

Submerged tanks

Floating tanks %

V ≤ 0,5

3

1,5

0

0,5 < V ≤ 1

3

3

0

1 < V ≤ 1,9

3

3

1

1,9 < V ≤ 7,6

3

7,6

1

7,6 < V ≤ 114

15

15

1,5

114 < V ≤ 265

15

23

1/4 of the total diameter of two adjacent tanks

265 < V ≤ 341

15

30

341 < V ≤ 454

15

38

454 < V ≤ 757

15

61

757 < V ≤ 3785

15

91

V > 3785

15

122

For the safe distance from the tank to protected objects within DM&SPDM storage facilities:

Tank Volume (m3) Safe Distance to Protected Objects (m)
Less than 1 1.5
Greater than 1 to 2.85 3.0
Greater than 2.85 to 45.6 4.5
Greater than 45.6 to 114 6.0
Greater than 114 to 190 9.0
Greater than 190 to 380 15.0
Greater than 380 to 1,900 24.0
Greater than 1,900 to 3,800 30.0
Greater than 3,800 to 7,600 40.5
Greater than 7,600 to 11,400 49.5
Greater than 11,400 52.5

More details can be found in Decree 25/2019/ND-CP of Vietnam's Government, effective from April 22, 2019.

- Thanh Lam -

>> CLICK HERE TO READ THIS ARTICLE IN VIETNAMESE

0 lượt xem



  • Address: 19 Nguyen Gia Thieu, Vo Thi Sau Ward, District 3, Ho Chi Minh City
    Phone: (028) 7302 2286
    E-mail: info@lawnet.vn
Parent company: THU VIEN PHAP LUAT Ltd.
Editorial Director: Mr. Bui Tuong Vu - Tel. 028 3935 2079
P.702A , Centre Point, 106 Nguyen Van Troi, Ward 8, Phu Nhuan District, HCM City;