What are regulations on safe distance from fuel dispencers to surrounding structures at ground-level gas stations in Vietnam?

What are regulations on safe distance from fuel dispencers to surrounding structures at ground-level gas stations in Vietnam? Thank you!

The safe distance from fuel dispencers to surrounding structures at ground-level gas stations in Vietnam must comply with the requirements specified at Point c Clause 1 Article 9 of Circular 15/2020/TT-BCT. To be specific:

The safe distance from fuel dispencers to surrounding structures at ground-level gas stations in Vietnam is regulated in Table 4.

Table 4: Safe distance from fuel dispencers to surrounding structures at ground-level gas stations

Construction Item Safe Distance (m) {not less than (2), (3)}

Level 1

Station

Level 2

Station

Level 3

Station

Production areas with fire or spark generating activities 18 18 18
High-density population areas (4) 50 50 50
Civil buildings and other construction structures outside the station (5) Fire resistance level (1) I, II 5 5 5
III 15 12 10
IV, V 20 14 14

Electric cable line

Telecommunication cable line

- According to current regulations on electrical safety corridor.

- According to current regulations of the telecommunications industry.

Notes:

(1) Fire resistance level of the structure according to QCVN 06:2020/BXD National Technical Regulation on Fire Safety for buildings and structures.

(2) Distance for tanks is calculated from the edge of the operation pit (tank neck).

(3) Distance for fuel dispencers is calculated from the center of the fuel dispencer.

(4) High-density population areas include: schools, hospitals, stadiums, markets, shopping centers, supermarkets, national exhibitions, train stations, bus stations, ports.(5) Distance for civil buildings is calculated to the building's boundary.

- The safe distances in Table 4 are allowed to be reduced by 30% when the station is equipped with a vapor recovery system for gasoline.

- The safe distance from storage tanks and fuel dispencers to high-density population areas is reduced to 25 meters (17 meters in case of a vapor recovery system) if the gasoline station is equipped with a fixed or semi-fixed firefighting system.

Best regards.

Related Posts
LawNet
What are regulations on the sitting position with firearms in a police vehicle in the Public Security Force's Ordinance in Vietnam?
LawNet
Requirements for Organizations and Individuals to Practice Veterinary Medicine
LawNet
Dossier Requesting Republication of Supplementary Food Product Information
LawNet
Dossier for Requesting the Disclosure of Information on Imported Supplementary Food Products
LawNet
Dossier for Requesting the Disclosure of Information on Domestically Produced Supplementary Food Products
LawNet
What is a Foundation Seed?
LawNet
Is Stunning Poultry Required Before Slaughter?
LawNet
Dossier on the Disclosure of Information for Complete Compound Feed Products, Concentrated Feed
LawNet
Rights and Obligations of Test Establishments for Animal Breeds and Lines
LawNet
Conditions for Contestants to Participate in Modeling Competitions
Lượt xem: 0
Latest Post

Đơn vị chủ quản: Công ty THƯ VIỆN PHÁP LUẬT.
Chịu trách nhiệm chính: Ông Bùi Tường Vũ - Số điện thoại liên hệ: 028 3935 2079
P.702A , Centre Point, 106 Nguyễn Văn Trỗi, P.8, Q. Phú Nhuận, TP. HCM;