Which establishments must install Automatic Fire Suppression System under the regulations in Vietnam?

Which establishments must install the Automatic Fire Suppression System under the current regulations? I want to learn on this issue to install Automatic Fire Suppression System in my establishments for fire prevention. Thanks for the advice!

What are the regulations on fire prevention and fighting equipment in Vietnam?

According to Article 37 of Decree 136/2020/ND-CP on fire prevention and fighting equipment as follows:

Article 37. Fire prevention and fighting equipment
1. Fire prevention and fighting equipment includes motor equipment, equipment, machines, tools, chemicals and support tools used for fire prevention and fighting as well as human and property rescue and mentioned in Appendix VI enclosed therewith.
2. Motor firefighting equipment of firefighting authorities are mentioned in Section 1 of Appendix VI enclosed therewith.
3. Requirements for domestically manufactured or imported fire prevention and fighting equipment:
a) They must meet technical specifications laid down for fire prevention and fighting purposes;
b) They are compliant with Vietnamese regulations and standards or foreign or international standards applicable in Vietnam.

Which facilities must install Automatic Fire Suppression System in Vietnam?

Pursuant to Vietnam Standard TCVN 3890:200 on fire prevention and fighting equipment for buildings and works, equipment, arrangement, inspection and maintenance are mentioned as follows:

7. Equipment, placement, checking and maintenance of automatic firefighting system
7.1. Equipment and placement of automatic firefighting system
7.1.1. The automatic firefighting system must be equipped for buildings and works specified in Annex C. The equipment of automatic firefighting system for other buildings and works based on the analysis of danger level of fire and factors relating to the protection of people and property.
In the buildings and works specified in Annex C, there should be an automatic firefighting system for all rooms not depending on area excluding the following areas:
- Wet areas (bathrooms, toilets, refrigerating chamber, washing area ...);
- Staircase;
- Areas without any danger of fire.

* Appendix C of this Vietnamese Standard is specifically as follows:

Appendix C (Regulation)

Buildings and Works equipped with Automatic Fire Suppression System

No.

Subject to be equipped

Requirement and norm index

1. Building



1

Warehouse:

- Materials and products with sulphur, cellulosic and alkali metal origin

- Wool, felt, leather, metals and precious stones;

- Films, pictures and video tapes in non-flammable packing with storage volume of 200 kg or more, and any volume in inflammable packing;

- Materials and semiconductors, IC and other electronic components;

- Motor, machinery, gap-bridging equipment including fuel and oil;

- Materials and goods of production class C on fire danger preserved on shelf of 5.5 m high or more.

No dependence on constructional area and a number of storeys

1.2

Preservation warehouse of natural rubber, synthetic rubber and rubber products

1.2.1

One-storey building

Total construction area of 750m2 or more

1.2.2

Building with one storey or more

No dependence on constructional area

1.3.

Preservation warehouse with two storeys or more preserving materials and goods of production class C on fire danger (excluding cases specified at Point 1.1 and 1.2)

No dependence on constructional area

1.4

Archives, libraries, preservation of statistic documents, handwritten historical documents and other valuable documents

No dependence on constructional area

1.5.

Building of 25m or more (excluding production building of production class D and E)

No dependence on area

1.6.

1-storey steel frame building with metal roof:

1.6.1

Public (*), collective, civil

Area of ​​800 m2 or more

1.6.2

Commercial (**)- Administrative

Area of ​​1200 m2 or more

1.7

Business building (**) (No installation of automactic firefighting system at areas of preservation and preparation meat, fish, vegetables and fruits in non-flammable packing; metal plates and bowls, non-flammable materials)

1.7.1

Underground

Area of 200m2 or more

1.7.2

One-storey buidling (excluding subjects specified at point 1.6)

Area of 3500m2 or more

1.7.3

Two-storey buidling

Area of 3500m2 or more

1.7.4

Three-storey buidling

No dependence on area

1.7.5

Business building of ignitable and inflammable liquid (excluding gas-station and solution contained in cans with volume of less than 20l of each can)

No dependence on area

1.8

Cultural buiding and combination (including cultural combination of combination of production building, warehouse and residential building)

No dependence on area and number of storeys

1.9

Exhibition and advertisement building:

1.9.1

One-storey building

Area from 1000 m2 or more

1.9.2

Building with two storeys or more

No dependence on area

2. Works



2.1

Cable works (cellars, trays, tunnels, wells, double floor, frame, casing ... used to wire power cables or communication cables) of the power plant.

No dependence on area

2.2

Other cable works with the voltage of 500 kV or higher

No dependence on area

2.3

Cable works with the voltage of 110KV connected to a transformer with a capacity of 63 KVA and above

No dependence on area

2.4

Works of connection cable of production buildings and civil buidlings

Over 100 m3

2.5

Mixed cable cellar of production buildings and civil buidlings in which cable or conductor with voltage of 220 V, the volume of cable cellar over 100 m3 with a number of cable:

12 strands or more

2.6

Closed or open conveyors transporting flammable materials

25 m long or more

2.7

Installation of suspended ceiling (Part of technical space) to install ventilation tube and water supply pipe and cable tray with more than 12 cable strands and a voltage of 220 V or higher insulated by flammable and non-flammable (including the wiring on the same holder)

No dependence on area and volume

2.8

Petroleum store and tanks of inflammable and combustible liquid

According to TCVN 4530, TCVN 5307, TCVN 5684.

3. Room and chamber



3.1. Room and chamber used for storage or production



3.1.1

Under production class A and B (excluding building of processing and preservation of agricultural grains)

Area of 300m2 or more

3.1.2.

Containing, storage and production materials and rubber products, wood (cellulose), sulphur, alkali metals, semiconductor materials, micro-circuits and other electronic components. Materials and products from wool, felt, leather, film, pictures and video tapes made ​​from combustible materials.

No dependence on area

3.1.3

Under production class C (excluding cases specified in 3.2):

3.1.3.1

In mezzanine or basement

No dependence on area

3.1.3.2

On the other storeys above ground

Area of 300m2 or more

3.1.4

Preservation and production of materials and products from aluminum ore, rubber adhesive, combustible and inflammable liquid products such as solvents, paints, adhesives, mastics, impregnation liquid, coating chamber, synthesis of synthetic rubber, compressors with gas turbine engines, oil and diesel oil heating chamber

No dependence on area

3.1.5

High voltage testing chamber, chamber partitioned by combustible materials

No dependence on area

3.2. Dynamic room and chamber



3.2.1

Transformer and compensator chamber from or 500KV or higher

No dependence on area

3.2.2

Transformer chamber with a voltage from 220 to 230 KV with capacity of each transformer from 200 MVA or higher

No dependence on area

3.2.3

Transformer chamber and circuit breaker in closed container:

3.2.3.1

With capacity of 63 MVA or more

No dependence on area

3.2.3.2

With a voltage of 110 kV or higher

No dependence on area

3.2. Communications room or chamber



3.3.1

Technical workshops of the terminal equipment, intermediate switching room, radio signal transmission and receiving center

No dependence on area

3.3.2

Digital switch chamber, telephone control center, computer and telegraph center of post office of provinces and cities with a total building area of 40,000 m3 or more

No dependence on area

3.3.4

Automatic switchboard with capacity of 10,000 subscribers, channels or junctions

No dependence on area

3.3.5

Division and connection room with computer use to control automatic switchboards with capacity from 10,000 inter-provincial and municipal channels or more.

Area of 24m2 or more

3.3.6

Room of handling, sorting, storage, packaging of letter, telegrams, telegraphs, newspapers

Area of 500m2 or more

3.4. Room and chamber of transport



3.4.1

Room and chamber used for manufacturing, repairing and processing train (electrical machines and equipment, repair and processing wagons, wheels, engines ...

No dependence on room and chamber area

3.4.2

Room and component works of the subway system (excluding the way of passenger carrying transfer station, battery room, water pump station, heating appliance, ventilating chamber)

No dependence on room and chamber area

3.4.3

Traffic control center with automatic systems, medium and high frequency radio communications center

No dependence on room and chamber area

3.4.4

Disassembly and installation room of aircraft engine, flight equipment, chassis and aircraft and helicopter wheels

Room removable aircraft engines, flight equipment, and Isaac si wheel aircraft, helicopters

No dependence on chamber area

3.4.5.

Repair and manufacturing room of aircraft engine

No dependence on room and chamber area

3.4.6

Room for placement of vehicles in a number of works (excluding in residential building):

3.4.6.1

Basement (including under bridges)

No dependence on room and chamber area

3.4.6.2

Mezzanine and overground floor

3 automobiles or more

3.4.7

Subway stop way with technical maintenance

4500m2 or more

3.5. Public performance room



3.1.5

Preservation and transaction room of large volume of publications, documents, manuscripts and other valuable materials (including records of the operating room)

No dependence on area

3.5.2

Library archive with reserve of 500 000 units of books and documents or more

No dependence on area

3.5.3

Exhibition space

Area of ​​1 000 m2 or more

3.5.4

Preservation and display room of value works of art and articles of museum

No dependence on area

3.5.5

Room and chamber with cultural and art functions:

3.5.5.1

Cinemas, clubs, theaters with size of stage 21m x 15m, regardless of the number of audience or stage with smaller size for design number of more than 700 audiences

No dependence on area

3.5.5.2

Concert room or combination of concert and movie with 800 seats or more

No dependence on area

3.5.5.3

Warehouse: props, scenery, stage tools, studio

No dependence on area

3.5.5.4

Studio

Area of ​​1 000 m2 or more

3.5.5.5

Preservation room of baggages, flammable material storage at railway station (including airport) arranged on storeys:

3.5.5.5.1

Basement, underground floor

No dependence on area

3.5.5.5.2

Overground floor

Area of ​​300 m2 or more

3.5.5.6

Preservation chamber and room of flammable or non-flammable materials in burnable packing placed at:

3.5.5.6.1

Under grandstand of roofed sports building

Area of ​​100 m2 or more

3.5.5.6.2

In roofed sports building with capacity of 800 seats or more

Area of ​​100 m2 or more

3.5.5.6.3

Under grandstand of outdoor sports building with capacity of 3000 seats or more

Area of ​​100 m2 or more

3.5.5.7

Master computer room, communications, preservatio of magnetic board, archival paper tape, recording equipment, technical room below the stage and studio.

No dependence on area

3.5.5.8

Chamber, commodity trading space in other performance buildings (residential or public building.... ) placed in:

3.5.5.8.1

Mezzanine and basement

Area of ​​200m2 or more

3.5.5.8.2

Other overground floors

Area of ​​500m2 or more

4. Equipment



4.1

There are coating chambers using ignitable or flammable liquid.

No dependence on type of equipment

4.2

There are drying chambers

No dependence on type of equipment

4.3

Recovery tower of flammable waste

No dependence on type of equipment

4.4

Transformer cooled with oil with a voltage:

4.4.1

A voltage of 500 KV

With any capacity

4.4.2

A voltage from 220 KV to 330KV

With capacity of 200 MVA or more

4.4.3

A voltage of 110 KV installed in hydropower plant

Capacity of generator is 63 MVA or more

4.5

Oil circuit-breaker in closed distribution equipment

With volume of oil from 60 kg or more

4.6

Electric power substations using diesel or gas generators designed on automobile or trailer

No dependence on area

4.7

Shelves with the height of over 5.5 m for preservation of flammable or non-flammable materials contained in burnable packing

No dependence on area

4.8

Tanks containing oil with containing capacity

3m3 or more


NOTE:

(*)Public buidling, ex: school, hospital, cultural and sports house...

(**) Building used for business, commerce or entertainment, for ex: market, commercial center, dancing hall...



What is the fine for cases without Automatic Fire Suppression System in Vietnam?

According to Clause 5, Article 41 of Decree 144/2021/ND-CP, the fine for cases without Automatic Fire Suppression System is:

Article 44. Violations against regulations on provision, storage and use of fire safety and firefighting equipment
...
5. A fine ranging from 15.000.000 VND to 25.000.000 VND shall be imposed for any of the following violations:
a) Failure to install the fire alarm and firefighting system as prescribed by law;
b) Failure to have firefighting apparatus as prescribed by law.

..."

The above fine is applied to an individual's administrative violation. For organizations with the same violations, the fine is twice the fine for individuals.