Vietnam: What are the details of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation?

“What are the details of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam?” - asked Ms. H.D (Hue)

What are the details of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam?

On February 28, 2023, National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam is issued with Decision 261/QD-BKHCN 2023 by the Vietnam Ministry of Science and Technology.

Accordingly, under Section 1 of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam as follows:

(1) This standard provides for installation and equipment of fire protection equipment, fire protection systems for buildings, constructions, urban areas, economic zones, industrial parks, industrial clusters, export-processing zones, hi-tech zones, and other dedicated areas as prescribed [5], when:

- The construction is carried out;

- The renovation aims to increase scale or repurpose rooms, buildings and constructions;

- The renovation aims to increase scale of economic zones, industrial parks, industrial clusters, export-processing zones, hi-tech zones and other dedicated areas according to regulations.

- Fire and explosion hazard classes of rooms, buildings and construction are changed in a manner that increases the fire hazard.

(2) In addition to complying with this standard, buildings and constructions shall comply with the technical regulation or standard specific to each type of building/construction. In the case of any discrepancy between this standard and other regulations, the more stringent regulations shall prevail.

(3) For buildings and constructions on which specific regulations are unavailable, foreign or international fire safety standards may be applied in accordance with prevailing regulations or guidelines of the ministerial fire authority.

What are the normative references of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam?

Under Section 1 of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam, the normative references on Fire protection - Fire protection equipment for building and construction - Equipment, Installation include:

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

TCVN 4530 Filling station - Specifications for design.

TCVN 4878 Fire protection - Classification of fires.

TCVN 4879 Fire protection - Safety signs.

TCVN 5307 Petroleum and petroleum products terminal - Design requirements.

TCVN 5738 Fire protection - Automatic fire alarm system - Technical requirements.

TCVN 5684 Fire safety for petroleum and petroleum products facilities - General requirements.

TCVN 5760 Fire extinguishing system - General requirements for design, installation and use.

TCVN 6100 Fire protection - Fire extinguishing media - Carbon dioxide.

TCVN 6101 Fire protection equipment - Carbon Dioxide extinguishing systems for use on premises Design and Installation.

TCVN 6223 Liquefied petroleum gas (LPG) store - Safety general requirements.

TCVN 6305 (all parts) Fire protection - Automatic sprinkler systems.

TCVN 7026 Fire fighting - Portable fire extinguishers - Performance and construction.

TCVN 7027 Fire fighting - wheeled fire extinguishers - Performance and construction.

TCVN 7161 (all parts) Gaseous fire - extinguishing systems - Physical properties and system design.

TCVN 7336 Fire protection - Water, foam automatic fire-extinguishing systems - Design and installation requirements.

TCVN 7435 (all parts) Fire protection - Portable and wheeled fire extinguishers.

TCVN 7568 (all parts) Fire detection and alarm systems.

TCVN 9255 Performance standards in building - Definition and calculation of area and space indicators.

TCVN 12110 Fire protection - Portable fire centrifugal pump with internal combustion engine - Technical requirements and test methods.

TCVN 12314 (all parts) Automatic activated fire extinguisher.

TCVN 13316 (all parts) Fire protection - Fire fighting vehicles.

TCVN 13332 Respiratory protective devices - Full face masks - Technical requirements and test methods.

TCVN 13333 Aerosol Fire-Extinguishing Systems - Specifications for design, installation, inspection and maintenance.

TCVN 13456 Fire protection - Emergency lighting and Exit sign - Design, installation requirements.

What are the regulations on equipment and installation of fire extinguishers for houses and buildings in Vietnam?

In subsection 5.1, Section 5 of National standard TCVN 3890:2023 on Fire protection - Fire protection equipment for building and construction - Equipment, Installation in Vietnam, the regulations on equipment and installation of fire extinguishers for houses and buildings in Vietnam are as follows:

- Equipment and installation of portable and wheeled fire extinguishers.

+ All areas in buildings and constructions, including areas equipped with fire extinguishing systems, must be equipped with portable or wheeled fire extinguishers.

+ The selection, equipment and installation of fire extinguishers shall comply with the regulations laid down in Articles 6 and 7 of TCVN 7435-1.

+ For narrow and long areas or areas with different and adjacent floor levels, a fire extinguisher must be installed so that the travel distance from the position of a fire extinguisher to the farthest point to be protected does not exceed that specified in 5.1.1.2.

+ On the same floor or storey, if the premises is separated into different areas by walls, partitions or other obstacles without any passageway, fire extinguishers must be installed separately in accordance with 5.1.1.2 and 5.1.1.3.

+ The number of fire extinguishers reserved must not be less than 10% of the total number of fire extinguishers intended for replacement where necessary (no more than 100 of each type).

+ Fire extinguishers must be placed in conspicuous and easily accessible locations and should be red. If it is difficult to identify them, signs that show their locations may be used and the regulations set out Article 5 of TCVN 7435-1 shall be complied with. Fire extinguishers must not be placed in a single location, except for the case where they are placed in a storage area in accordance with 5.1.1.5.

Fire extinguishers should be always available for immediate use and located:

++ where they will be readily seen by any person following an escape route;

++ most suitably, near to room exits, stairways, corridors, and passage-ways;

++ in similar positions on each floor, where floors are of similar appearance.

Fire extinguishers should not be located:

++ where a potential fire might prevent access to them;

++ close to heating appliances that might affect quality and efficiency of the extinguishers;

++ in concealed positions behind doors, in cupboards or deep recesses;

++ where they might cause obstruction to exit routes;

++ in positions in rooms or corridors away from exit routes unless they are necessary to cover a particular hazard;

++ where they might be damaged by daily activities.

+ Portable and wheeled fire extinguishers must have the functions and meet the specifications specified in TCVN 7026 and TCVN 7027.

- Equipment and installation of hanging type automatic diffusion dry-powder fire extinguishers

+ Hanging type automatic diffusion dry-powder fire extinguishers must conform to TCVN 12314-1.

+ Based on the actual conditions of buildings and constructions, they may be wall or ceiling mounted with an appropriate height to effectively cover the area to be protected as announced by the manufacturer. In any case, the distance from the temperature sensor to the ceiling should not exceed 40 cm.

+ Hanging type automatic diffusion dry-powder fire extinguishers may be installed in kitchen areas of restaurants, boiler rooms and laundry areas with an area not exceeding 100 m2. If installed in an area of more than 100 m2, it is recommended that such area be divided into areas by a fire-separating wall (with a fire-resistance rating at least REI 45) or a fire separating partition (with a fire-resistance rating at least EI 45), each of which must not exceed 100 m2.

- Equipment and installation of automatic activated fire extinguishers - fire suppression cylinders

+ Automatic activated fire extinguishers - fire suppression cylinders must conform to TCVN 12314-2.

+ An automatic gas fire extinguishing system may be replaced with an automatic activated fire extinguisher - fire suppression cylinders (design it in such a way that the discharge monitoring function is added and discharge signals are transmitted to the fire alarm control panel) in normally unoccupied areas with an area not exceeding 100 m2. If installed in an area of more than 100 m2, it is recommended that such area be divided into areas by a fire-separating wall (with a fire-resistance rating at least REI 45) or a fire-separating partition (with a fire-resistance rating at least EI 45), each of which must not exceed 100 m2.