On December 28, 2017, the Vietnam Ministry of Construction issued Circular 15/2017/TT-BXD specifically enumerating the requirements for air conditioning equipment in buildings.
Circular 15 stipulates that air conditioning equipment and chillers in Vietnam must have a minimum Coefficient of Performance under standard assessment conditions and not be less than the values stated in the two tables below:
Table of Coefficient of Performance for Direct Electric-Powered Air Conditioners in Vietnam
Equipment Type |
Cooling Capacity, kW |
COPMin, kW/kW |
Testing Procedure |
1 Cluster Air Conditioner |
- |
2,80(*) |
TCVN 6576:2013 TCVN 7830:2015 TCVN 10273-1:2013 |
2 Cluster Air Conditioner |
< 4.5 |
3,10(*) |
|
≥ 4.5 and < 7.0 |
3,00(*) |
||
≥ 7.0 and < 12.0 |
2,80(*) |
||
Air-cooled air conditioner |
≥ 14 and < 19 |
3,81 |
TCVN 6307:1997 |
≥ 19 and < 40 |
3,28 |
ARI 340/360 |
|
≥ 40 and < 70 |
3,22 |
||
≥ 70 and <223 |
2,93 |
||
≥ 223 |
2,84 |
||
Water-cooled air conditioners |
< 19 |
3,54 |
ARI 210/240 |
≥ 19 and < 40 |
3,54 |
ARI 340/360 |
|
≥ 40 and < 70 |
3,66 |
||
≥ 70 and < 223 |
3,63 |
||
≥ 223 |
3,57 |
||
Steam-cooled air conditioner |
< 19 |
3,54 |
ARI 210/240 |
≥ 19 and < 40 |
3,54 |
ARI 340/360 |
|
≥ 40 and < 70 |
3,51 |
||
≥ 70 and < 223 |
3,48 |
||
≥ 223 |
3,43 |
||
Air-cooled condenser assemblies |
≥ 40 |
3,07 |
ARI 365 |
Condenser assemblies cooled by water, or steam |
≥ 40 |
3,95 |
|
NOTE: COP = Cold Yield / Power Consumption, kW/kW. The condenser assembly consists of a compressor and a condenser; (*) 1 cluster or 2 cluster air conditioners: the energy efficiency of the equipment is evaluated by the Cooling Seasonal Performance Factor (CSPF) instead of the Coefficient of Performance. The process of testing and evaluating the equipment's energy efficiency is carried out per TCVN 7830:2015, TCVN 6576:2013 and TCVN 10273-1:2013 (ISO 5151:2000). |
Table of Coefficient of Performance for Chillers
Equipment Type |
Air-cooled air conditioner, kW |
COPMin, kW/kW |
Air-cooled, electric chiller. Attached or detached condenser |
All |
2,80 |
Piston chiller, water cooling, electric |
According to the requirements of Spiral and Screw Chiller, water cooling, electric |
|
Spiral and screw chiller, water cooling, electric |
< 264 |
4,51 |
≥ 264 and < 528 |
4,53 |
|
≥ 528 and < 1055 |
5,17 |
|
≥ 1055 |
5,67 |
|
Centrifugal chiller, water cooling, electric |
< 528 |
5,55 |
≥ 528 and < 1055 |
5,55 |
|
≥ 1055 and < 2110 |
6,11 |
|
≥ 2110 |
6,17 |
|
Air Cooling Absorption Chiller, 1 Level |
All |
0,60(*) |
Water Heat Absorption Chiller, 2 Levels |
All |
0,70(*) |
Absorbent chiller, 2 levels. Indirect burning |
All |
1,00(*) |
Absorbent chiller, 2 levels. Direct Burning |
All |
1,00(*) |
COMMENT: (*) For absorption air conditioners, Coefficient of Performance = Cold Yield / Heat Consumption Capacity; Evaluation of the performance of the absorption chiller, using the ARI 560 standard; The water cooler feature is rated to ARI 550/590 standard. |
Details may be found in Circular 15/2017/TT-BXD effective from June 1, 2018.
- Thao Uyen -
Address: | 19 Nguyen Gia Thieu, Vo Thi Sau Ward, District 3, Ho Chi Minh City |
Phone: | (028) 7302 2286 |
E-mail: | info@lawnet.vn |