Distance for Fire Prevention and Fighting in the Area for Fuel Transportation Vehicles in Vietnam

Below is a notable content regulated in Circular 12/2018/TT-BXD promulgating the National Technical Regulation on Car Garages, code QCVN 13:2018/BXD in Vietnam.

According to the provisions of Circular 12/2018/TT-BXD, vehicles carrying fuels and lubricants are only allowed to be stored in open yards or in separate one-story buildings with a fire resistance level not less than level II of grade S0.

Additionally, the fire prevention and fighting distance for the land area used for storing vehicles carrying fuels and lubricants in Vietnam must meet the following requirements:

Total volume of flammable liquids, m3 Distance from truck garage to buildings and constructions and distance between truck garages, m
Building and fire resistance
I, II III IV, V
Over 1,000 to 2,000 30 30 36
From 600 to 1,000 24 24 30
Less than 600 18 18 24
Up to 300 18 18 24
Less than 300 12 12 18

See the full text of the provisions at Circular 12/2018/TT-BXD, effective from March 15, 2019.