The minimum performance of water heaters in Vietbnam regulated by Circular 15 is as follows:
Type of Equipment
|
Minimum performance ET, %
|
Gas-fired hot water storage heaters
|
78
|
Gas-fired instantaneous water heaters
|
78
|
Gas-fired hot water supply boilers
|
77
|
Oil-fired hot water supply boilers
|
80
|
Gas and oil-fired hot water supply boilers
|
80
|
Boilers with a thermal power capacity of 10-350 kW, burning wood and paper
|
60
|
Boilers with a thermal power capacity of 10-2000 kW, burning brown coal
|
70
|
Boilers with a thermal power capacity of 10-2000 kW, burning stone coal
|
73
|
Electric-resistance water heating units
|
Emin = 5.9 + 5.3V0.5 (W)
|
NOTES:
- The minimum performance of gas or oil-fired water heating units is given as thermal efficiency, which includes heat loss from the unit's compartments;
- The minimum performance of electric-resistance water heating units is determined from the maximum standby loss (SL) when the temperature difference between the heated water and the surrounding environment is 40°C. In the above formula, V is the volume measured in liters;
- Testing procedure to be conducted according to ANSI Z21.10.3 standards or other applicable standards for the project.
|
|
Details may be found in Circular 15/2017/TT-BXD effective from June 1, 2018.