On December 28, 2017, the Vietnam Ministry of Construction issued Circular 15/2017/TT-BXD promulgating the National Technical Regulation on Energy Efficiency Buildings.
The Lighting power density in energy-consuming buildings in Vietnam is stipulated by Circular 15 through the following table:
Type of Building |
Lighting power density (W/m 2 ) |
---|---|
Office |
11 |
Hotel |
11 |
Hospital |
13 |
Medical Center, Health Care* |
11 |
Library* |
14 |
Conference* |
15 |
School |
12 |
Commercial, Service |
16 |
Residential |
8 |
Warehouse* |
9 |
Indoor Parking Area |
3 |
NOTES: - (*) Items within the types of buildings under the scope of the Regulations; |
Details may be found in Circular 15/2017/TT-BXD effective from June 1, 2018.